Page 54 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS 7ML1998MV01
mmmmm
Commissioning
1.2. Pump Control
Use this wizard to configure pumps if they will be used in your application. Be sure to
first complete the applicable Quick Start Wizard.
a. Press RIGHT arrow to activate PROGRAM mode and open menu level 1: MAIN
MENU.
b. Press RIGHT arrow to navigate to menu item 1.1.
c. Press DOWN arrow and RIGHT arrow to open Pump Control.
d. At each step, press DOWN arrow to accept default values and move directly to
the next item,
or RIGHT arrow to open Edit mode: the current selection is highlighted.
e. Scroll to desired item and press RIGHT arrow to store the change, then press
DOWN arrow to continue.
f. At any time, you can press UP arrow to go back, or LEFT arrow to cancel
the wizard.
Start of Wizard - Pump Control
Shows the type of Wizard to be executed.
Number of Pumps
Select the number of pumps to be used with pump control.
If set to NONE, pump control is disabled.
Relay Pump 1
Selects the relay assigned to Pump 1.
Relay Pump 2
View only. Automatically sets the relay assigned to Pump 2 based on relay selected
for Pump 1 in previous step.
Note: The introduction screen is displayed only on the device when using the local
push buttons. This screen is not part of the Quick Start when using SIMATIC PDM.
Options
CANCEL, START
Options
NONE, 2
Default: NONE
Options
RELAY 2, RELAY 3
Default: RELAY 2
Options
(view only)
If Relay Pump 1 = RELAY 2, then Relay Pump 2 = RELAY 3
If Relay Pump 1 = RELAY 3, then Relay Pump 2 = RELAY 2