A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 149
mmmmm
Parameters
2.6.2. Volume Units
Determines volume measurement units used when 2.1.2.Sensor Mode set to
VOLUME.
2.6.3. Maximum Volume
The maximum volume of the vessel. Enter the vessel volume corresponding to
High Calibration Point. For example, if your maximum vessel volume is 8000 L,
enter a value of 8000.
2.6.4. Dimension A
The height of the vessel bottom when the bottom is conical, pyramidal,
parabolic, spherical, or flat -sloped. If the vessel is horizontal with parabolic
ends, the depth of the end. See Vessel Shape (2.6.1.) for an illustration.
Defined in
2.1.1.Units
.
2.6.5. Dimension L
Length of the cylindrical section of a horizontal parabolic end vessel. See
Vessel Shape (2.6.1.) for an illustration.
Defined in
2.1.1.Units
.
2.6.6. User Defined Unit
Set the unit text to display for current volume when 2.6.2.Volume Units set to
user-defined.
Limited to 16 ASCII characters.
Options
*L (Litres)
USGAL (US Gallons)
IMPGAL (Imperial Gallons)
CUM (Cubic Meters)
USER DEFINED (units defined in
2.6.6.User Defined Unit
)
Values
Range: 0.0 to 9999999
Default: 100.0
Values
Range: 0.000 to 99.999
Default: 0.000
Values
Range: 0.000 to 99.999
Default: 0.000
Note: The text entered is simply for display purposes. No unit conversion
occurs.