Configuration
6.2 Configuring the busbar run layout
SIVACON 8PS - Configuring with LX system
118 Configuration Manual, 10/2011, A5E02194899-02
Vertical busbar run layout between infeed and end cap, Case 4
● Expansion compensation unit is not required in the topmost sub-run to the end cap.
● Position further expansion compensation units in the centre between the fixed points.
()
)3
)3
//
/
/
'
'
L1 Max. permissible sub-length
L2 Halved max. permissible sub-length
L Total run length
D Expansion compensation
FP Fixed point (type: LX-BVFP..)
EF End cap
Examples of power distribution with LXA...., (LXC....)
Run length L
[m]
Number of fixed points (FP) Number of expansion
compensation units (D)
≤ 6 (≤ 6) 0 0
≤ 25 (≤ 30) 0 1
≤ 75 (≤ 90) 1 1
≤ 125 (≤ 150) 2 2