Product selection
4.3 Selection tables
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
63
4.3.4.2 Tap-off units with fuse switch disconnector up to 630 A
Equipment features
● Can be connected under load
1)
● Tap-off via tap-off point
● Degree of protection IP54, increased to IP55 with installation kit
● Tap-off units LX-AK5/FSH...
– Can only be connected on systems LX...3., LX...4. and LX...5.
● Tap-off units LX-AK6/FSH...
– Connection device for insulated PE conductor
– Can only be connected on systems LX...6.
● Cable connection
– Single conductor cable connection
2)
only for tap-off units from 400 A
3)
– Multi-core cable connection for the systems LX...52, LX...54 and LX...62 maximum
connection cross-section only to 100% neutral conductor
● Cable entry
– Front: Tap-off units up to 250 A
– Side and front: Tap-off units from 315 A to 630 A
1)
Please observe national regulations. Connection under load may not be permissible.
2)
Aluminium plate undrilled, cable glands provided by the customer, see Technical data
(Page 125)
3)
For 125 A to 250 A on request