1-3
Note 1: When the system displays “1.02.xx”, this indicates the revision level of the boot software and does not
indicate the revision level of the panel’s BIN file. Refer to “Determining the BIN File Software Revision,” in
Appendix C of this manual for additional information.
Note 2: Revision 1 systems containing greater than 175 TrueAlarm isolator devices may reboot at this point. If this
occurs, upgrade the BIN file and programmer software to Rev. 2. Refer to Appendix A.
Note 3: Keep the following in mind about mismatched CFIG and BIN files:
- If a Rev. 2 job (CFIG) is downloaded to an SFIO board containing a Rev. 1 BIN file, the system reverts to a
Rev. 1 factory default job.
- If a Rev. 1 job (CFIG) is downloaded to an SFIO board containing a Rev. 2 BIN file, the system reverts to a
Rev. 2 factory default job.
Note 4: The SFIO board must be factory adjusted, tested, and loaded with the latest version of BIN file prior to
shipment. If a new SFIO board is received in the field and there is no BIN file loaded on it (i.e., a system with a
new SFIO enters a continuous link scan/code scan loop), this indicates that the board has not been factory adjusted
and tested. Order a new SFIO board, call Service Support to report the problem, and refer to Appendix B of this
manual for information on brownout potentiometer adjustment.
Note 5: The BIN file is available on the FTP site, the Technical Services Intranet site, or by ordering
Simplex Part # 741-108.
Initial Power Up Flow Chart, Continued
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing