3-2
Table 3-1. Crash Codes
Code Corrective Action
Crash Code =0D
PC = BD76
A pulse statement in Custom Control does not have an analog
pseudo point referenced to it. Fix the CC equation.
Crash Code = 0D
PC = BA09
This is a known problem with Version 1.02. Upgrade panel to
Revision 2.01
0 Code not supported by 4010.
1 Replace SFIO.
2 Code not supported by 4010.
3 Reload application.
4 Reload application.
5 Reload application or replace SFIO.
6 Reload application or replace SFIO.
7 Reload application or replace SFIO.
8 Reload application or replace SFIO.
9 Replace SFIO.
A Keypad is missing. Check keypad connections / Replace SFIO.
B
Indicates a mismatch between BIN file and programmer software.
Upgrade BIN file and programmer software to same revision.
C Reload job. Check versions of 4010 Programmer and BIN file.
D Reload job. Check versions of 4010 Programmer and BIN file.
E Reload job. Check versions of 4010 Programmer and BIN file.
F Code not supported by 4010.
10
This can be caused by using the PC programmer to assign a point
type of unavailable to a NAC or 24 point I/O point. This code can
also be caused by selecting an RIAM (relay IAM) device type for an
IAM. Make changes and reload job. Check versions of 4010
Programmer and BIN file.
11
May indicate that a not available device type was selected for a
signal circuit. Reload job. Check versions of programmer and BIN.
12 Replace SFIO.
13 Replace SFIO.
14 Reload application.
15 Reduce cards/reload job.
16 Reload BIN File.
17
18 Replace SFIO.
19
1A Reload CFIG. Check versions of 4010 Programmer and BIN file.
Continued on next page
Summary of Crash Codes
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing