2-17
Table 2-10. Digital Pseudo Point Troubles
Point Label Description
D4 Extra N2 Card
Turned on at panel startup if an unprogrammed N2 slave card is
detected. Only clears on panel restart.
D5 External N2 Trouble
Turns on when panel is no longer communicating with ALL slave
cards. Turns off on a System Reset.
D7 Cold Start
Indicates that panel has performed a cold start. Turns of when
acknowledged.
D8
Warm Start / Check
Time and Date
Indicates that panel has performed a warm start. Turns off when
acknowledged.
D10
System Time and
Date
Indicates that the time and date is incorrect. Turns off when time and
date is updated.
D11
Simplex Service
Mode
Indicates that the panel is in Service Mode. Turns off only on a panel
restart.
D13 Active List Overflow
Turns on when the number of alarms, supervisories, or troubles is
greater than the system active list size (100 fires, 50 supv, 300
troubles). Turns off on a panel restart.
D14 City Disconnect On if city circuit is disconnected.
D15 City Circuit Trouble On if city circuit is in trouble.
D17
Control Point
Bypass
On if control points are bypassed.
D18 Elevator Bypass On if elevator recall points are bypassed.
D19 Doorholder Bypass On if doorholder points are bypassed.
D20
Verification Tally
Limit Exceeded
On when any verified points tally limit exceeds10. Off when all points
tally limit is below 10.
D21
Walk Test Active in
System
On when Walk Test is active.
D23
TrueTest Active in
System
On when TrueTest is active.
D24
Programming Mode
- System Disabled
On when Programming or Quick-CFIG is entered. Panel is no longer
operational.
D45
Duplicate IDNet
Device Detection
Active
When on (either through front panel or SMPL) it enables the duplicate
device detection diagnostic on the IDNet card.
D47
Event Queue
Overflow
On when the RS232/LCD annunciator event queue is overflowed and
events have been missed. Panel restart clears the trouble, or you can
manually turn D47 OFF. See “Clearing an Event Overflow Trouble” in
Appendix C for information on turning off this point.
D48
LCD Annunciator
Sounder Disable
When on the panel tells all LCD Annunciators to disable their local
sounder. Turning pseudo off will enable the sounders. Controllable
from front panel only- not SMPL.
Digital Pseudo Point Troubles
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing

Related product manuals