1-2
System Displays:
"1.02.xx"
System Displays:
Crash Code A?
System Displays:
Any other
Crash Code
Check cable running from keypad to
SFIO Board.
Replace SFIO Board
System Displays:
"Link Scan" followed by
"Code Scan
C123456789A"
System Displays:
"Warm Start Trouble"
Press ACK Key
AC Power LED ON
System
Displays:
Continuos Link Scan/
Code Scan Loop?
Bin File Corrupt, Damaged, or Missing
Replace BIN File or Replace SFIO.
See Note 4.
No Other Troubles or
Crash Codes Present
System Displays:
Crash Codes
See
AC Power
Flowchart
YES
NO
YES
NO
NO
YES
NO
YES
NO
Do Additional Troubles
Appear?
NO
Do Crash Codes Appear?
Refer to Crash Codes in Chapter 3
Refer to Trouble Descriptions in
Chapter 2
System Displays:
"System is Normal"
YES YES
Refer to
Crash Codes
in Chapter 3
NO
YES YES
YES
YES
YES
System Displays:
CFIG Format Mismatch
(~ 10 Seconds)
Versions of Programmer
and BIN File do not match.
See Note 3 Below.
YES
NO
See Note 2
See Note 1
Initial Power Up Flow Chart