Document: LT0400 4100U-S1 Programming Guide
Appendices
Issue 1.4 15 December 2010 Page 12-19
ZONE n Isolate
[INPUTS]
STATUS FIRE
L260+n | LIST | MIXED | ALARM LIST ZONE n
AND NOT STATUS ON
P600+n | DIGITAL | SUPERV | ISOLATE ZONE n
[END INPUTS]
[OUTPUTS]
TRACK ON PRI=9,9
P800+n | DIGITAL | UTILITY | ALARM ZONE n
[END OUTPUTS]
ZONE n New Alarm and LED Flash
[INPUTS]
CONTINUE
AND STATUS FALMACK
L260+n | LIST | MIXED | ALARM LIST ZONE n
[END INPUTS]
[OUTPUTS]
FLASH SLOW
X-X | LED | LED | AZFn LED (See table)
TRACK ON PRI=9,9
P512 | DIGITAL | UTILITY | A ZONE ALARM LED IS FLASHING
[END OUTPUTS]
ZONE n Ack’ed Alarm and Steady LED
[INPUTS]
NOT STATUS FALMACK
L260+n | LIST | MIXED | ALARM LIST ZONE n
OR STATUS ON
P600+n | DIGITAL | SUPERV | ISOLATE ZONE n
AND STATUS FIRE
L260+n | LIST | MIXED | ALARM LIST ZONE n
[END INPUTS]
[OUTPUTS]
FLASH ON
X-X | LED | LED | AZFn LED (See table)
[END OUTPUTS]
ZONE n Alarm LED Off
[INPUTS]
NOT STATUS FIRE
L260+n | LIST | MIXED | ALARM LIST ZONE n
[END INPUTS]
[OUTPUTS]
FLASH OFF
X-X | LED | LED | AZFn LED (See table)
[END OUTPUTS]