4100U-S1 Programming Guide Document: LT0400
Adding Zone Displays
Page 7-6 15 December 2010 Issue 1.4
7.4 Modify the Custom Control Equations for the Zones
The simplest method to add more custom control equations for the new displays is to open a
32 or 64 zones template and export the custom control equations for the zones, then from
within the original site configuration import these equations. The detailed steps are as follow:
1. Click on theFile‟ menu and select „Open‟.
Browse to the location containing the 3 default configuration templates supplied with
SF0369 and select the S1_64ZN.SDB4100U configuration if more than 32 zones (up to 64)
are needed, or select S1_32ZN.SDB4100U if the configuration should include up to only 32
zones. Click OK.
2. Click on the Custom
Controltab. Right Click on
Program 4 and select „Export
Program….
Save the exported .CC4100U
file in an accessible location. .
At the end of the export process a message with the
process status will appear with the export result.
Click the OK button.
3. Close the template and re-open the site configuration database.
4. Click on the „Custom Control‟ tab.
Right Click on Program 4 and selectImport, Append Program….
Browse to the location where you saved the exported .CC4100U file, select it and click
Open’.
The import process will start.
At the end of the import process, a message with the process status will appear with the
import result.
Click the OK button.