4100U-S1 Programming Guide Document: LT0400
Appendices
Page 12-4 15 December 2010 Issue 1.4
12.2.2 Analog Points
Analog Points can have a value 0-65535 and can be used for Timers, Counters or store a
numerical value.
A0 Number of Devices in Alarm
A1 Number of Isolates
A2 Number of Faults
A34 System Startup pulse
A257 Alarm and Fault Test Timeout
12.2.3 Lists
Lists are container objects used to group several points. A list inherits the states and status
of the points within the list and the list is used the same as a point.
L256 Brigade call Alarm List
L257 General Fire Trip List (ACF Isolatable)
L258 Zone Alarm Test List
L259 Zone Fault Test List
L260 Zone Isolate Toggles
12.2.4 Physical Hardware Points (LEDs Relays etc)
Alarm Test Active LED or keyboard panel (P514)
A/C Trip LED (P521)
ACF Isolated LED (P517)
Bells Isolated LED (P518)
0-5-10 Warning System Isolated LED (P519)
0-5-11 Common Alarm LED
0-5-13 Fault Test Active LED (P515)
0-5-1 Alarm Fault Normal Button (P513)
0-5-2 A/C Reset Button (P522)
0-5-3 ACF Isolate Button (P517)
0-5-4 Bell Isolate Button (P518)
0-5-5 Warning System Isolate Button (P519)
0-7-3 City Alarm Relay
0-7-4 City Alarm Trouble Relay (FAULTS)
1-9 City Fire Relay 1 (ALARMS)
1-11 City Supervisory Relay 2 (ISOLATES)
1-12 City Trouble Relay 3 (FAULTS)
SIG3 ACF General Fire Trip (SPS NAC 1)
SIG4 Fire Alarm Bell (SPS NAC 2)
SIG5 Warning System (SPS NAC 3)