4100U-S1 Programming Guide Document: LT0400
Addressable Device Settings
Page 6-4 15 December 2010 Issue 1.4
6.3.2 4090-9001 Supervised Input IAM and 4090-9051 Encapsulated Input
IAM
Device Type
IAM – Standard setting
Point Type
FIRE – General Fire Point.
UTILITY – Input used by Custom Control Logic only
TROUBLE – Input used to indicate a Fault status
6.3.3 4090-9002 Relay IAM
Device Type
RIAM – Standard Setting
Point Type
RELAY – General Purpose relay.
TRELAY – Fault Relay on until fault cleared
6.3.4 4090-9101 Monitor ZAM
Device Type
MBZAM – Standard Setting
Point Type
FIRE – Standard setting
6.3.5 4190-9050 4-20mA Analog Monitor ZAM
Device Type
ANAMON – Standard Setting
Point Type
The Point Types are custom configurable using the AMON Pt Type Tab. The Point
types need to be configured before the 4190-9050 is added.
6.3.6 4090-9118 Relay IAM with T-Sense Input
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point
Device Type
TRIAM – Standard setting
Point Type
UTILITY – Standard setting
Mx-x-1 1
st
Sub Point (relay output)
Device Type
MRELAY – Fixed Device type
Point Type