Document: LT0400 4100U-S1 Programming Guide
Addressable Device Settings
Issue 1.4 15 December 2010 Page 6-3
6.2.4 4098-9754E Multi-Sensor Photo Heat Detector (COMBO)
Mx-x-0 Parent Point
Device Type
COMBO – Standard Multi-Sensor detector on standard base
ICOMBO – Standard Multi-Sensor detector on Isolator base
SCOMBO – Standard Multi-Sensor detector on Sounder base
Mx-x-1 1
st
Sub Point
Device Type
MPHOTO – Standard setting
Point Type – Photo Part
SMOKE – Standard setting
VSMOKE – Verified Smoke Detector (Recommended setting to reduce nuisance
alarms)
DUCT – Duct detector
Mx-x-2 2
nd
Sub Point
Device Type
MHEAT – Standard setting
Point Type – Heat Part
MHEAT – Standard setting
MOHEAT – Standard heat detector with Rate of Rise
Mx-x-3 3
rd
Sub Point
Device Type
MARCOR – Default not used in Australia
CAUTION DO NOT USE MARCOR SETTING NOT CSIRO ACTIVFIRE LISTED
Point Type – R-Correlation Part
FCOR – Alarm Smoke / Heat Correlation
UCOR – Utility Smoke / Heat Correlation used for non-MAF usage only
Device Type
MAOFF – Standard setting used in Australia
Point Type – R-Correlation Part
UTILITY – Standard setting
6.3 Addressable Device Settings
Any unused points should be set as utility to avoid potential false alarms from unused fire
point type inputs.
6.3.1 4099-9032 MCP
Device Type
KACPULL – Standard MCP
Point Type
PULL – Standard setting