Document: LT0400 4100U-S1 Programming Guide
Addressable Device Settings
Issue 1.4 15 December 2010 Page 6-3
6.2.4 4098-9754E Multi-Sensor Photo Heat Detector (COMBO)
Mx-x-0 Parent Point
Device Type
COMBO Standard Multi-Sensor detector on standard base
ICOMBO Standard Multi-Sensor detector on Isolator base
SCOMBO Standard Multi-Sensor detector on Sounder base
Mx-x-1 1
st
Sub Point
Device Type
MPHOTO Standard setting
Point Type Photo Part
SMOKE Standard setting
VSMOKE Verified Smoke Detector (Recommended setting to reduce nuisance
alarms)
DUCT Duct detector
Mx-x-2 2
nd
Sub Point
Device Type
MHEAT Standard setting
Point Type Heat Part
MHEAT Standard setting
MOHEAT Standard heat detector with Rate of Rise
Mx-x-3 3
rd
Sub Point
Device Type
MARCOR Default not used in Australia
CAUTION DO NOT USE MARCOR SETTING NOT CSIRO ACTIVFIRE LISTED
Point Type R-Correlation Part
FCOR Alarm Smoke / Heat Correlation
UCOR Utility Smoke / Heat Correlation used for non-MAF usage only
Device Type
MAOFF Standard setting used in Australia
Point Type R-Correlation Part
UTILITY Standard setting
6.3 Addressable Device Settings
Any unused points should be set as utility to avoid potential false alarms from unused fire
point type inputs.
6.3.1 4099-9032 MCP
Device Type
KACPULL Standard MCP
Point Type
PULL Standard setting