Document: LT0400 4100U-S1 Programming Guide
Addressable Device Settings
Issue 1.4 15 December 2010 Page 6-5
RELAY – General Purpose relay
TRELAY – Fault Relay on until fault cleared
Mx-x-2 2
nd
Sub Point (T-Sense input)
Device Type
MTSENSE – Fixed Device type
Point Type
FIRE – General Fire Point
UTILITY – Input used by Custom Control Logic only
TROUBLE – Input used to indicate a Fault status
WATER – Sprinkler -Flow Switch setting
WSO – Sprinkler – Flow Switch and Valve Monitor
6.3.7 4090-9119 Relay IAM with Unsupervised Input
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point
Device Type
FRIAM – Standard setting
Point Type
UTILITY – Standard setting
Mx-x-1 1
st
Sub Point (relay output)
Device Type
MRELAY – Fixed Device type
Point Type
RELAY – General Purpose relay
TRELAY – Fault Relay on until fault cleared
Mx-x-2 2
nd
Sub Point (feedback input)
Device Type
MFEEDBK – Fixed Device type
Point Type
UTILITY – Input used by Custom Control Logic only
TROUBLE – Input used to indicate a Fault status
6.3.8 4090-9120AU 6 Point I/O Module (4 Inputs, 2 Relay outputs)
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point