Document: LT0400 4100U-S1 Programming Guide
Appendices
Issue 1.4 15 December 2010 Page 12-23
System Lists
Point
Label
L18
GENERAL FIRE ALARM MONITOR ZONES
Stores the number of physical alarm type points connected to the
panel.
L76
VARIABLE SENSITIVITY PHOTO ANALOG SENSOR
Stores the number of TrueAlarm Photo detectors connected to the
panel.
L77
VARIABLE SENSITIVITY ION ANALOG SENSOR
Stores the number of TrueAlarm Ionization detectors connected to
the panel.
L78
ANALOG SENSORS WITH PIEZO
Stores the number of TrueAlarm detectors with Piezo (Sounder)
bases connected to the panel.
L79
ANALOG SENSORS WITH RELAY
Stores the number of TrueAlarm detectors with Relay bases
connected to the panel.
System Analog Pseudo Points
Point
Label
A98
BATTERY TROUBLE COUNTER
Stores the number of times a Battery Fault has been detected
since last reboot.
A99
AC POWER FAIL COUNTER
Stores the number of times a Mains Fail Fault has been
detected since last reboot.
A112
GROUND TROUBLE COUNTER
Stores the number of times an Earth Fault has been detected
since last reboot.
A115
EXCESSIVELY DIRTY (OUT OF RANGE)
Stores the number of Excessively Dirty detectors.
A116
DIRTY SENSOR COUNTER
Stores the number of Dirty detectors.
A117
ALMOST DIRTY COUNTER
Stores the number of Almost Dirty detectors.