Document: LT0400 4100U-S1 Programming Guide
Appendices
Issue 1.4 15 December 2010 Page 12-11
3-14 Alarm and Fault Test Mode OFF
[INPUTS]
STATUS ON
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
AND STATUS ON
P515 | DIGITAL | UTILITY | FAULT TEST
[END INPUTS]
[OUTPUTS]
HOLD OFF PRI=9,9
P515 | DIGITAL | UTILITY | FAULT TEST
HOLD OFF PRI=9,9
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
HOLD OFF PRI=9,9
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
PRINT PANEL "ALARM and FAULT TEST OFF"
HOLD OFF PRI=7,7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
[END OUTPUTS]
3-15 Alarm and Fault Test Timer
[INPUTS]
STATUS ON
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
AND NOT STATUS ON
L258 | LIST | DPSEUDO | ALARM TEST LIST
AND NOT STATUS ON
L259 | LIST | DPSEUDO | FAULT TEST LIST
DELAY CONSTANT 60
A257 | Analog Timer | ANALOG | TIMER | ALARM and FAULT TEST TIMEOUT
[END INPUTS]
[OUTPUTS]
HOLD OFF PRI=9,9
P514 | DIGITAL | UTILITY | ALARM TEST
HOLD OFF PRI=9,9
P515 | DIGITAL | UTILITY | FAULT TEST
HOLD OFF PRI=9,9
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
HOLD OFF PRI=7,7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
[END OUTPUTS]
3-16 Reset Alarm and Fault Test
INPUTS]
STATUS ON
L258 | LIST | DPSEUDO | ALARM TEST LIST
AND NOT STATUS ON
P514 | DIGITAL | UTILITY | ALARM TEST
SAVE 1
STATUS ON
L259 | LIST | DPSEUDO | FAULT TEST LIST
AND NOT STATUS ON
P515 | DIGITAL | UTILITY | FAULT TEST
OR RECALL 1
OR STATUS ON
P0 | DIGITAL | UTILITY | SYSTEM RESET KEY
OR STATUS ON
P210 | DIGITAL | UTILITY | NETWORK DETECTOR RESET
OR STATUS ON
P212 | DIGITAL | UTILITY | DETECTOR/SYSTEM RESET
[END INPUTS]
[OUTPUTS]
HOLD OFF PRI=9,9
L258 | LIST | DPSEUDO | ALARM TEST LIST
HOLD OFF PRI=9,9
L259 | LIST | DPSEUDO | FAULT TEST LIST
[END OUTPUTS]