Maintenance
5.3
Symptom: NO COMMUNICATION
Probable Source of Trouble:
Terminal Connections
Check the terminal interface connection of the configurator.
Check if the interface is connected to the wires leading to the transmitter or to the terminals
[ + ] and [ - ].
Check if the interface is HPI311 – M5P models (for Hart protocol).
Transmitter Connections
Check if connections are according to wiring diagram.
Check if there is resistance in the 250 Ω line. See load limitation in Section 1.
Power Supply
Check output of power supply. The voltage at the LD301 terminals must be between 12 and 45
Vdc, and ripple less than 500 mV.
Electronic Circuit Failure
Locate the failure by alternately testing the transmitter circuit and the interface with spare parts.
Transmitter Address
Check if the transmitter address is compatible with the one expected by the configurator.
Symptom: CURRENT in 21.0 mA or 3.6 mA
Probable Source of Trouble:
Pressure Tap (Piping)
Verify if blocking valves are fully open.
Check for gas in liquid lines or for liquid in dry lines.
Check the specific gravity of process fluid.
Check process flanges for sediments.
Check the pressure connection.
Check if bypass valves are closed.
Check if pressure applied is not above upper limit of the transmitter range.
Sensor to Main Circuit Connection
Sensor connection to the Main Board.
Check connection (male and female connectors).
Electronic Circuit Failure
Check the sensor circuit for damage by replacing it with a spare one.
Replace sensor.
Symptom: INCORRECT OUTPUT
Probable Source of Trouble:
Transmitter Connections
Check power supply voltage.
Check for intermittent short circuits, open circuits and grounding problems.
Noise Measurement Fluid
Adjust damping
Pressure Tap
Check for gas in liquid lines and for liquid in steam or gases lines.
Check the integrity of the circuit by replacing it with a spare one.
Calibration
Check calibration of the transmitter.