Deactivation
either by changing the status of the control input,
or by pressing the validation key on the product keypad or D20,
or after a genset starting timeout,
or at the end of the timer (if set),
or if the source I is lost,
or in case of genset shutdown upon fault.
13.7.2.1. On load test (M-G application only)
This test is only possible in automatic mode, it enables you to start the genset and simulate a complete transfer
sequence.
Description
The purpose of this sequence is to execute a load transfer to the genset to test it, while adhering to
switchover conditions.
The time delays for validating the transfer conditions (TOT, 2ST, 2AT, 0DT, 2CT) are derived according to their
conguration.
The “retransfer conrmation” function is always active throughout an on load test. It enables transfer back to
source I in case of an unlimited on load test, or interrupts a time delayed on load test.
Activation
either via the operating menu,
or via the D20 interface,
or via the programmable input,
or via communication (for version with COM).
Deactivation
either by changing the status of the control input
or by pressing the validation key on the product keypad or D20
or after a genset starting timeout
or at the end of the timer (if set)
or in case of genset shutdown upon fault
13.7.2.2. Changeover switch position I, 0 and II check (accessible in AUT mode)
1 2
Description
Electrical operation of the changeover switch to reach position: PS1, PS0, PS2.
Activation
either via the operating menu. It will then be possible to force one of the positions I, O, II via the keypad,
or via the D20 interface,
or via the programmable input,
or by via communication (for version with COM).
Deactivation
either via the Escape key
or by switching from Auto mode to Man. mode.
The control takes priority over all functions.