EasyManua.ls Logo

socomec ATyS - IP Rating; Operating Conditions

socomec ATyS
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
EN
ATyS / ATySr - 541630C - SOCOMEC
5.3. Environmental
The ATySrproductmeetsthefollowingenvironmentalrequirements:
5.3.1. IP Rating
ø 1 mm
IP2XagainstdirectcontactfortheATySrmotorizationcontrolunit.
IP2X against direct contact for the power section with the connections in place and when including
suitable, correctly installed incoming and outgoing terminal shields.
IP 0 for the bare power section without terminal shields in place.
5.3.2. Operating Conditions
5.3.2.1. Temperature
From -20 to +40°C without derating
From -20 to +70°C when applying a Kt derating correction factor
Kt: Correction Factor Temperature
0.9 40°C…50°C
0.8 50°C…60°C
0.7 60°C…70°C
*Simpliedderatingmethod:Ithu≤IthxKf
*Amoreprecisecalculationmaybedoneforspecicapplications.Shouldthisberequiredpleasecontact
SOCOMEC.
5.3.2.2. Hygrometry
80%humiditywithoutcondensationat55°C
95%humiditywithoutcondensationat40°C
5.3.2.3. Altitude
Up to 2000m in altitude without derating
For higher altitude the Ka correction factors below apply
Ka: Correction Factor 2000m < A ≤ 3000m 3000m < A ≤ 4000m
Ue 0.95 0.8
Ie 0.85 0.85
5.3.3. Storage Conditions
5.3.3.1. Temperature
From -40 to +70°C

Table of Contents

Other manuals for socomec ATyS

Related product manuals