34
EN
ATyS / ATySr - 541630C - SOCOMEC
7.2.3. ATySr input and output contacts
7.2.3.1. Terminal denomination, description and characteristics.
All pressure on the connector
pins is to be avoided during
wiringoftheauxiliarycables
Control Enable: 312
Override to OFF: 313
Sw to Pos II I/P: 314
Sw to Pos I I/P: 315
Sw to Pos 0 I/P: 316
Common: 317
Prod Avail Common 63A
Prod Avail O/P: 64A
PosIIAuxContact: 24
PosIAuxContact: 14
Pos0AuxContact: 04
Common: 13
Power I/P L: 301
Power I/P N: 302
DENOMINA-
TION
TERMI-
NAL
DESCRIPTION CHARACTERIS-
TICS
RECOMMENDED
CABLE SECTION
SIGNALISA-
TION OUT-
PUTS
13 CommonI-0-IIforAuxContacts
DryContacts
2AAC1/250V
1.5mm
2
04 AuxContactPosition0-NormallyOpenContact
14 AuxContactpositionI:NormallyOpenContact
24 AuxContactpositionII:NormallyOpenContact
63A Product Available : Normally Open Contact. Closed when
theATySrisinAutomodeandmotorisationisoperational.
(No Fault powered and ready to changeover)
64A
ADDITIONAL
AUX CONTACT
INCLUDED
WITH 2000A
TO 3200A
OPTIONAL
FOR
800A TO 1600A
81 CommonforAuxContactspositionsI
DryContacts2A
AC1 / 250V
1.5 – 2.5mm
2
82 AuxContactpositionI:NormallyClosedContact
84 AuxContactpositionI:NormallyOpenContact
91 CommonforAuxContactspositionsII
92 AuxContactpositionII:NormallyClosedContact
94 AuxContactpositionII:NormallyOpenContact
POWER SUP-
PLY INPUT
301 Power supply – L
208 - 277VAC
±20%:50/60Hz
1.5mm
2
302 Power supply – N
CONTROL
INPUTS
312 Remote Control Mode Enable when closed with 317
Attn:
Donotconnectto
any Power supply
Maxcablelength
100m
1.5mm
2
313 Position0orderifclosedwith317.(Priorityorderinput
forcingtheproducttoremotecontrolmodeand0position)
314 Position II order if closed with 317
315 Position I order if closed with 317
316 Position 0 order if closed with 317
317 Common control terminal for 312 - 316 ATySr(Specic
VoltageSupply)
CAUTION
Do not connect terminals 312 to 317 to any power supply. These order inputs are
powered through terminal 317 and external dry contacts ONLY.