5.3.5. CE marking
The ATySrcompliesthewiththeEuropeandirectivefor:
• TheElectromagneticcompatibilityno.2004/108/CEdated15thofDecember2004.
• Lowvoltagedirectiveno.2006/95/CEdated12thofDecember2006.
5.3.6. Lead free process
• The ATySrcomplieswiththeEuropeandirectiveforRoHS.
5.3.7. WEEE
The ATySrisbuiltinaccordancewith2002/96/CEdirective:
5.3.8. EMC standard
The ATySrisdesignedandbuiltinaccordancewithIEC60947-1standards
(Productsintendedtobeinstalledinan«Industrial,Commercialand/orResidentialEnvironment»thereforerespectingboth
ClassAaswellasClassBEMCrequirements).
DESCRIPTION STD (IEC) REQUIREMENT (CRITERIA)
Conducted CISPR 11 Class B
Radiated CISPR 11 Class B
ESDcontact 61000-4-2 4KV(B)
ESDair 61000-4-2 8KV(B)
Electromagneticeld 61000-4-3 10V/m(A)
RF Conducted 61000-4-6 10V(A)
Burst 61000-4-4
2KV(B)power
1KV(B)control
Surge Common 61000-4-5 2KV(B)
Surge differential 61000-4-5 1KV(B)