13MT2 15MT2 13MT3 15MT3
Ambient
conditions
Protection type IP65
Ambient temperature range
(at rated output power)
−20 °C…+60 °C (−20 °C…+50 °C)
Relative humidity 0…100 % (condensation)
Maximum altitude above
sea level
2 000 m
3)
Noise emissions ( 1.5 m)
51 dB(A) fan off / 58 dB(A) fan on
Conguration Display Graphic LC display with backlight and status LED
DC disconnector integrated (cat. DC-21 or higher)
Circuit type two-stage, transformerless
Data logger Data logger for energy yield, peak output, and operating dura-
tion for the last 31 days, 12 months and 10 years
Fault current monitoring internal, AC/DC sensitive
Casing Aluminium
Overvoltage conductor DC Requirement class C (VDE 0675-6) and/or
type 2 (EN 61643-11)
Overvoltage conductor AC Requirement class D (VDE 0675-6) and/or
type 3 (EN 61643-11)
Standards &
guidelines
EMC EN 61000-3-2 / EN 61000-3-3 / EN 61000-3-11 / EN 61000-
3-12 / EN 61000-6-2 / EN 61000-6-3
Grid connection
2)
VDE-AR-N 4105 / VDE 0126-1-1 A1:2012 / BDEW MS-
Richtlinie / CEI 0-21 / CEI 0-16 / RD 661 / RD 1699 / G59/3 /
G83/2 / PPC Guide / C10/11 / EN 50438 / AS 4777
Device safety
IEC / EN 62109-1/-2
Interfaces Data communication RS485 / Ethernet
Status signalling contact M12 connector with relay as N/C contact / N/O contact
Connection of external grid
monitoring
M12 connector
Weight &
dimensions
Weight 39 kg 39 kg 42 kg 42 kg
Dimensions in mm
(W x H x D)
550 x 750 x 200
Warranty Standard 5 years / extension to 10, 15, 20, or 25 years possible
1) for AC rated power output
2) max. 700 V with external power limitation
3) contact us if the installation location is at a higher level
4) certicates are not available for all models. Details can be found at www.solarmax.com