Operation on LCD
»
PeakLimits1: Default:0 W, range: 0-60000 W
Once the consumption (grid side) reaches this value, the inverter will start
shaving to keep the consumption lower than this value.
»
ShavingStartTime: Default: 7:00
The battery starts discharging to shave consumption from the set time.
»
ShavingEndTime: Default: 15:00
The battery stops discharging at the set time.
==Peak shaving mode==
>DisChgPeriod1
DisChgPeriod2
ChargeFromGrid
===DisChgPeriod1===
ShavingStartTime
07:00
===DisChgPeriod1===
ShavingEndTime
15:00
===DisChgPeriod1===
PeakLimits1
10000W
DisChgPeriod2: Same wokring logic with DisChgPeriod1
»
PeakLimits2: Default:0 W, range: 0-60000 W
»
ShavingStartTime: Default: 19:00
The battery starts discharging to shave consumption from the set time.
»
ShavingEndTime: Default: 23:00
The battery stops discharging at the set time.
ChargeFromGrid: It can be used in specific time period. This period
allows inverter to take energy from grid to charge battery in order to have
enough backup for peak shaving. Please note that this period starts from
ShavingEndTime2, end until ShavingStartTime1.
»
Enable: Activate the function of ChargeFromGrid to allow the inverter taking
grid energy to charge battery. The ChargePowerLimits and MAX_SOC will
be displayed only when ChargeFromGrid is enabled.
»
ChargePowerLimits: Default: 1000 W; range: 0-60000 W
Settable target power taken from grid. Inverter will use this target power
taken from grid to charge battery.
»
MAX_SOC: Default: 50%; range: 10%-100%
Inverter will take grid energy to charge battery until battery SOC reaches this
value.