Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-170-
Running command
channel switch-
over sequence of
QUICK key
When P07.02=6, set the switch-over sequence of
running command channel.
0: keypad control→terminal control→ communication
control
1: keypad control←→terminal control
2: keypad control←→communication control
3: terminal control←→communication control
Stop function
selection of
STOP/RST key
Validness selection of stop function of STOP/RST.
For fault reset, STOP/RST is valid under any situation.
0: valid only for panel control only
1: valid for both panel and terminal control
2: valid for both panel and communication control
3: valid for all control modes
Frequency display
coefficient
0.01–10.00
Display frequency=running frequency× P07.08
Speed display
coefficient
0.1–999.9%
Mechanical speed=120×display running
frequency×P07.09/number of motor pole pairs
Linear speed
display coefficient
0.1–999.9%
Linear speed=mechanical speed×P07.10
Temperature of
rectifier bridge
module
Temperature of
inverter module
Software version
of control board
High bit of VFD
power
consumption
Display the power consumption of the VFD.
VFD power consumption=P07.15×1000+P07.16
Setting range of P07.15: 0–65535 kWh (×1000)
Setting range of P07.16: 0.0–999.9 kWh
Low bit of VFD
power
consumption
0x0000–0xFFFF
Bit0–bit3 Inverter type
0x0: G type
0x1: Reserved
Bit4–bit11: Chip type and manufacturer
0x00: DSP(TI)