36
Step 3 Install the OT/DT terminal to the wire and crimp them with a crimping tool. Install a heat
shrink tubing to the terminal and heat it with a heat gun.
Step 4 Secure the OT/DT terminal to the copper bar by M12 x 45 bolts with a tightening torque of
60- 70 N.m.
• If copper wires are used, fasten the bolt assembly as shown below.
figure 6-1 Copper Wire Connection
• If aluminum wires are used, fasten the bolt assembly as shown below.
figure 6-2 Aluminum Wire Connection
6 Electrical Connection System Manual