10.2 Other Faults
Fault Detail Possible Cause Corrective Method
The inverter shuts
down shortly after
startup
The DC input voltage is
just enough to start the
inverter. If the inverter is
connected to loads, and
the voltage cannot meet
the requirements, caus-
ing the inverter to shut
down.
Design and connect the battery pan-
el series based on the recom-
mended open-circuit voltage,
increase the DC voltage input, and
avoid applying the critical voltage
value.
Upper computer com-
munication failure
There are many possible
reasons, please check
one by one according to
the description of "Cor-
rective Method”.
Check whether the local address,
baud rate, and other parameters on
the interface are consistent with
those on the host computer.
Check whether all wiring is good. If
RS485 communication is adopted,
check whether the A and B terminals
are connected reversely.
Replace the communication adapter
and try again if the communication
adapter does not match.
If the fault is not caused by the fore-
going reasons and still persists,
please contact SUNGROW as soon
as possible.
WiFi connection unre-
sponsive/failed
Equipment is not
compatible.
1. Refresh the Web page manually.
2. Restart or replace the mobile de-
vice and try connecting again.
3. Power off and restart the inverter
to connect again.
10 Troubleshooting System Manual

Table of Contents

Other manuals for Sungrow MVS4480-US

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow MVS4480-US and is the answer not in the manual?

Sungrow MVS4480-US Specifications

General IconGeneral
BrandSungrow
ModelMVS4480-US
CategoryInverter
LanguageEnglish

Related product manuals