Model AT 5000 AT 4500 AT 3600 AT 2700
Insulation, frequency and DC cur
-
rent monitoring
integrated according to DIN VDE 0126-1-1
Required phases, number of grid
connections
3 (L1, L2, L3, N, PE)
Number of feed-in phases (230 V
single-phase)
1
Performance
Stand-by consumption 6,5 W
Night-time consumption < 0,06 W
Maximum efficiency
95,5% 95,5% 95,5% 95,5%
European efficiency
95,0% 95,0% 94,9% 94,7%
MPP efficiency (static)
99,99% 99,99% 99,99% 99,99%
Switching concept HERIC® / FP topology, transformerless
Other
DC switch internal, mechanical
Grid-connection fuse layout 25 A 25 A 25 A 16 A
Data interfaces
Ethernet, CAN, RS485, voltageless alarm relay, S0
pulse output, modem
Sensor interfaces irradiation, temperature
LCD, backlit, 128 x 64 pixels
Display
Plant supervision
active alarm via e-mail, integrated web-server, Sun
-
ways Communictor, Sunways Portal
IP degree of protection accord
-
ing to IEC 60529
IP 54
132
Model AT 5000 AT 4500 AT 3600 AT 2700
Max. relative humidity
95%
Cooling free convection
Ambient temperature -25°C...40°C (at full load)
Overload behaviour working point adjustment
Dimensions (height x width x depth) 59 x 35 x 21 cm
Weight 29 kg
Type of installation wall installation
Noise development < 35 dB (A)
Standard warranty (option) 5 years (10 years)
Certicates CE, DIN VDE 0126-1-1