Tens place:
0: Light overmodulation; restricted in zone 1
1: Heavy overmodulation; restricted in zone 2
For inverters of 1PH 220V/3PH 380V (≤2.2kW)
and 3PH 220V (≤0.75kW), the default value is
00;
for those of 3PH 380V (≥4kW) and 3PH 220V
(≥1.5kW), the default value is 01.
0x0000–0x1223
Ones place: frequency enable selection
0: Both ∧/∨ keys and analog potentiometer
adjustments are valid
1: Only ∧/∨ keys adjustment is valid
2: Only analog potentiometer adjustments is
valid
3: Neither ∧/∨ keys nor digital potentiometer
adjustments are valid
Tens place: frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency setting modes
2: Invalid for multi-step speed when multi-step
speed has the priority
Hundreds place: action selection during stopping
0: Setting is valid
1: Valid during running, cleared after stopping
2: Valid during running, cleared after receiving
the stop command
Thousands place: ∧ / ∨ keys and analog
potentiometer integral function
0: The Integral function is valid
1: The Integral function is invalid
0x000–0x221
Ones place: frequency control selection
0: UP/DOWN terminals setting valid
1: UP/DOWN terminals setting invalid