p
Model 880 DEPOSITION CONTROLLER
y
SECTION 6.XX
e page 256 of 276 ^
Mnemonic: EXCT_mrxstat
Parameters: none.
Description: Queries Model 880 for current status of Memory Module.
Returns: Numeric value 0, 1 , 2 for not installed, installed, bogus. Bogus means system is menu
hung until a clear key is pressed.
[RZCD_AOK] if proper parameter value was sent.
[RZCD_ILDV] if improper value for parameter arguments.
[RZCD_ILSN] if too many arguments, wrong delimiters, etc.
Command i
Response A0
Description Memory Module not installed.
______________________________________________________________________
Command: ^
Mnemonic: EXCT_trapinfo
Parameters: ? or ! with no delimiters or U followed by ? or ! for UIFC.
Description: sys_trap information display (?), clear (!).
Returns:
[RZCD_AOK] if proper parameter value was sent. If was a ^? or ^U? query then returns a result
of the form:
J,N
where J and N are major and minor sys_trap numbers whose meaning is dependent on
the source code. Values of 0,0 indicate no captured error states.
[RZCD_ILDV] if 2nd character (parameter) is other than ? or ! or U ; or if 2nd character is a U
and third character is other than ? or !.
[RZCD_ILCD] if command expression too long or too short (more than correct trailing parameters
or missing any argument parameter info).
Examples:
^?
query current state of SCUP sys_trap error codes. Returns valid reply per syntax above such as:
A1,2
^! clear sys_trap error codes to 0,0 . Armed to get new error conditions. Replies with just the
RZCD_AOK value.
^ missing needed argument, returns RZCD_ILCD.
^ABC More argument than needed, returns RZCD_ILCD.
^4 Argument wrong value, returns RZCD_ILDV.
______________________________________________________________________
Command: j
Mnemonic: EXCT_flush
Parameters: =2001
Description: Flush non-vol and reboot as if a Service-Purge performed. The syntax of the j command
allows spaces around the '=' operator. The numeric value of 2001 is a security key to
insure that the function is only activated intentionally to purge parameter, sequencing,
process accounting and I/O memory.
Returns:
[RZCD_AOK] if proper parameter value was sent. Unit will reboot after approximately 2 seconds,
and recover to a runtime mode with the system 'hung' in a state which requires user
acknowledgement (via front panel or RS232 event) before deposition can occur.