7 Using the product
78
Enter the recipient’s email address.
If an alarm chain is to be created from several recipients, the output
targets (SMS or email) of the recipients must not be different within the
respective alarm chain.
Transfer alarm settings
Exit "Alarm management" menu.
Alarm settings are transferred to the instruments.
7.2.6.5 Creating alarm rule
No configuration changes are transferred to the Saveris probe/base
until you have exited the Alarm management menu!
You should therefore exit the Alarm management menu after any
changes.
A prerequisite for creation of alarm rules is that the Saveris base alarm settings,
the alarm groups of the Saveris probes and the recipients of the alarm
messages have been entered.
Click on Alarm management in the navigation area.
The following submenus are displayed in the data area:
• Alarm settings base
• Alarm settings component
• Alarm settings channel
• Alarm recipients
• Alarm rules
• Comments for acknowledging alarms
A list of the previously created alarm rules is shown in the display area.