PM077 R1 09/08/20 Page 34 THOMSON TECHNOLOGY
Measurement table (read only) function code 04h.
Scaling Addr Content Unit
J1939 ADEC MDEC
Description
629 EIC exch. temp A [deg] [F] - 1/10 - Exh. temp bank A
630 EIC exch. temp B [deg] [F] - 1/10 - Exch. temp bank
B
631 EIC Winding 1 temp [deg] [F] - 1/1 - Gen winding 1
temp
632 EIC Winding 2 temp [deg] [F] - 1/1 - Gen winding 2
temp
633 EIC Winding 3 temp [deg] [F] - 1/1 - Gen winding 3
temp
634 Reserved - - - - -
635 Reserved - - - - -
636 EIC Turbo 1 compr
outlet press
[bar] [psi] - 1/10 - Turbo 1 compr
outlet press
637 EIC Intercooler temp [deg][F] - 1/10 - Intercooler temp
638
EIC trip fuel_gaseous
[kg] 1/1 - -
Trip fuel, gaseous
639 EIC total fuel
used_gaseous
[ton] 1/10 - - Total fuel used,
gaseous
640
EIC engine trip fuel
[L] 1/1 - -
Engine trip fuel
641 EIC engine total fuel
used
[kL] 1/10 - - Engine total fuel
used