4.8.3 Chiller alarms unusually
Chiller lcd panel is showing normal, but the red light on and buzzer beeping.
Here are the reasons:
Water is not enough
Please check the water level of chiller, like below:
Keep the water level in the green area
Water circulation pipes are blocked or water pump break down
Please connect a water hose between water inlet and outlet on chiller to check the water
circulation, like below.
Does alarm stop
If alarm stops, so maybe the water hose in the laser machine was blocked somewhere, please