Usage example 1 ··· 3-wire operation (one-push operation)
Use the 3-wire operation function to operate the inverter, maintaining operation without using the sequence circuit
by inputting an external signal (reset logic signal).
F
CC
S2
Forward run
Reverse run
HD
R
Forward run (F) : Pressing forward run (F) rotates forward at
the specified frequency command value.
Reverse run (R) : Pressing reverse run (R) rotates in reverse
at the specified frequency command value.
HD (S2): Pressing HD (S2) decelerates and stops.
R
F
HD
Power
Supply
Note 2)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Forward
Reverse
0
Note 3)
Output
frequency
Note 1) Set  = (ST: standby) and  = (terminal board) for 3 wire operation. Assign HD
(operation hold) to any input terminal at input terminal selection. When assigning the S2 terminal
as shown above, set  =  (HD: operation hold).
Note 2) If the terminals are ON before turning on the power, terminal input is ignored when the power is
turned ON. (Prevents sudden movements.) After turning the power ON, turn terminal input ON
again.
Note 3) When HD is OFF, F and R are ignored even when ON. R does not operate even if it's ON when
HD is ON. Likewise in this state, F does not operate even if it's ON. Turn F and R OFF and then
turn them ON.
Note 4) During 3 wire operation, sending the jog run mode command stops operation.

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required

Related product manuals