F3 Control Parameters
【F3.00】 Holding
Frequency
The drive accelerates to the holding frequency and then operating in constant
speed. The setting range is 0.00~400.00Hz
【F3.01】 Holding Time Interval
The operation time of drive running at the holding frequency, and the setting range
is 0.0~360.0sec. Using the frequency setting and holding time is to prevent the over
slip of motor causing over-current and stall.
Holding freq.
(F3.00)
Holding time interval
(F3.01)
Output freq.
Time
【F3.03】 Stall Prevention Level at the Acceleration
If stall is occurred during acceleration, the motor keeps running at the constant
speed (200%: Off), and the setting range is 30%~200% of drive’s rated current
【F3.04】 Stall Prevention Level at the Constant Speed
If stall is occurred at constant speed running, the motor decelerates (200%: Off),
and the setting range is 30%~200% of drive’s rated current
【F3.05】 Acceleration Time for Stall Prevention at the Constant Speed
Setting the acceleration time for the stall prevention of the constant speed, and the
setting range is 0.1~3200.0 sec.
【F3.06】 Deceleration Time for Stall Prevention at the Constant Speed
Setting the deceleration time at the stall prevention of the constant speed, and the
setting range is 0.1~3200.0 sec.
【F3.07】 Deceleration Stall Prevention
0: Deceleration stall prevention: Disabled
1: Deceleration stall prevention: Enabled