Frame construction, size-dependent,
Ä
Chapter 5.6.1 ‘General’ on page 47
Distance of FKR-EU to a FK-EU 75 – 225 mm (flange construction 80 – 225 mm)
Mortar-based installation into a lightweight partition wall, below a flexible ceiling joint
Fig. 39: Mortar-based installation into a lightweight partition wall, below a flexible ceiling joint
1 FKR-EU
2.1 Mortar
3.2 Lightweight partition wall with metal support
structure, cladding on both sides
3.6 Compartment wall or safety wall with metal sup-
port structure, cladding on both sides
4.1 Solid ceiling slab
5.1 Dry wall screw
6.5 Mineral wool (depending on wall construction)
6.13 Mineral wool strips, filler as an alternative (if
required to even out an uneven wall)
7.1 UW section
7.10 Trim panels
7.21 Ceiling joint strips (e.g. 4 × 10 mm)
Z Spigot construction 370 mm
Flange construction 342 mm
# Depending on the wall structure
Up to EI 90 S
Note: representative illustration. The distance to the ceiling depends on the design of the flexible ceiling joint, the
expected ceiling subsidence and the specifications of the wall manufacturer.
Additional requirements: mortar-based installation
into lightweight partition and compartment walls
Lightweight partition wall or compartment wall,
Ä
on page 34
Installation
Lightweight partition walls > Mortar-based installation
Fire damper FKR-EU58