EasyManua.ls Logo

Unitronics Unistream URD-0800 - URA-0004 W (AO04 W) - 4 Analog Current Outputs 12 Bit

Unitronics Unistream URD-0800
164 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4/19
Unitronics
110
URA-0004W (AO04W) - 4 Analog Current Outputs 12bit
Items
Specification
Outputs per module
4 Outputs single ended
Indicators(Logic side )
4 Green Output Status LEDs
Resolution in Ranges
12 bits : 4.88uA/bit
Output Range
0~20mA
Data Format
16bits Integer (2’s complement )
Module Error
±0.1% Full Scale @ 25°C (77°F) ambient
±0.3% Full Scale @ -40°C to 70°C (-40°F to 158°F)
Load Resistance
Max. 250Ω *
Dignostic
Field Power Off : LED Blinking
Field Power On : No Output LED Off
Field Power On : Output LED ON
Conversion Time
Max. 150usec / All Output
Calibration
Not Required
Common Type
4 Channels / 4 Common
Power Dissipation
Max. 30mA @ 5VDC
Isolation
I/O to Logic : Photocoupler Isolation
Field power : Non-Isolation
Field Power
Supply Voltage : 24VDCnominal
Voltage Range : 18 to 32VDC
Power Dissipation : Max. 80mA @ 24VDC
Wiring
I/O Cable Max. 2.0
(AWG 14)
Weight
58g
Module Size
12mm x 99mm x 70mm
* Operating temperature
--40°C to 70°C (-40°F to 158°F) temperature range specification can be guaranteed under the following conditions.
- Load Resistance : Min 100Ω, Max 250Ω
- Otherwise, temperature specification can be guranteed with -40°C to 60°C (-40°F to 140°F)