URA-0800O (AI08O) - 8 Current Inputs
8 Inputs single ended, non-isolated between inputs
12 bits : 4.88uA/Bit(0~20mA), 3.91uA/Bit(4~20mA)
16bits Integer (2' compliment)
±0.1% Full Scale @ 25 ºC (77°F) ambient
±0.3% Full Scale @ -40 ºC, 70 ºC (-40°F, 158°F)
Diagnostic Field Power Off : LED Blinking
Field Power On : LED Off < 0.5% (Maximum Input Value)
Field Power On : LED On > 0.5% (Maximum Input Value)
Maximum Range Over : LED Off > 21mA
Minimum Range Over : LED Off < 3mA ( 4 ~ 20mA)
≤ 1msec / All channel (≤ 0.125ms per channel)
2 Common, Field Power 0V is Common(AGND)
I/O to Logic : Isolation
Field power : Non-Isolation
Supply Voltage : 24VDC nominal
Voltage Range : 18 to 32VDC
Power Dissipation : Max. 30mA@24VDC
I/O Cable Max. 2.0
(AWG 14)
-40°C to 70°C (-40°F to 158°F)