4.3.1 Basic and Advanced User Modes
You can switch between the Basic Mode and Advanced Mode user modes with the selections
in the Settings menu.
Certain functionalities are only available in Advanced Mode. The options enabled by switching
to Advanced Mode are often intended for administrative users: set the user mode according to
the requirements of the personnel that use the device.
4.4 Configuring Analog Outputs with Insight
Note that the humidity output parameter selected with the DIP
switches on the transmitter component board will be used instead of the
parameter selected with Insight. When using Insight to configure the output, set
all humidity parameter selection DIP switches on the transmitter component
board to the OFF position (left) to ensure they do not cause a conflict with the
Insight settings.
CAUTION!
If you use Insight to set both analog output channels to output T measurement,
the humidity parameter DIP switches do not have an eect on the output.
Figure 14 Analog Output Configuration Options in Insight