Integer Values (x100, Non-metric)
1)
392 0187
hex
Enthalpy 16-bit signed
integer
Btu/lb
1) NOTE: 16-bit integers have a maximum value of +32767. Certain measurement parameters
(for example, mixing ratio and enthalpy) can exceed this value in x100 scaling. In such cases,
the value of the parameter is cut o at +32767, and measurements above this value are not
reported. Verify that the measurement ranges in your application are suitable for the 16-bit
integer format with x100 scaling; whenever possible, it is recommended to use 32-bit float
values.
A.2 Status Registers
Table 13 Modbus Status Data Registers (Read-Only)
Register
Number
(Decima
l)
Address
(Hexade
cimal)
Register Description Data Format Bitmask
513 0200
hex
Device status 16-bit signed integer 0000
hex
:Status OK
0001
hex
: Critical error,
maintenance needed.
0002
hex
: Error, device may
recover automatically
0004
hex
: Warning
0008
hex
: Notification
0010
hex
: Calibration mode
active
514 0201
hex
Error code 32-bit signed
integer
0201
hex
(status code low): see
Table 14 (page 52)
0202
hex
0202
hex
(status code high): see
Table 15 (page 52)
516 0203
hex
Security hash 32-bit signed
integer
Security hash changes on any
change to device settings/
adjustments.
0204
hex
Appendix A – Modbus Registers
51