Technical description
4 Measurement functions
4.1 Measurement accuracy
VM265.EN011
119
4.1. Measurement accuracy
Phase current inputs I
L1
, I
L2
, I
L3,
I’
L1
, I’
L2
, I’
L3
Measuring range
25mA 250 A (5A)
5mA 50 A (1A)
Inaccuracy I 7.5 A
0.5 % of value or 15 mA
I > 7.5 A
3 % of value
The rated input I
N
is 5A or 1A. It is specified in the order code
of the relay.
The specified frequency range is 45 Hz 65 Hz.
Residual current inputs I
01
, I
02
Measuring range
0 5 xI
N
Inaccuracy I 1.5 xI
n
0.3 % of value or 0.2 % of I
N
I > 1.5 xI
n
3 % of value
The specified frequency range is 45 Hz 65 Hz.
The rated input I
n
is 5A or 1A. This must be specified when
ordering the relay.
Frequency
Measuring range
16 Hz 75 Hz
Inaccuracy
10 mHz
In VAMP 265 frequency is measured from current signals.
THD and harmonics
Inaccuracy I 0.1 PU
2 % units
Update rate
Once a second
The specified frequency range is 45 Hz 65 Hz.