EasyManua.ls Logo

VAMP 265 - Example

VAMP 265
220 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.3 Calculating the stabilizing
resistance RS, VDR value and actual
sensitivity
7 Applications
Technical description
158
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
7.3.4. Example
CT
=
2000/1
V
KP
= 100 V
I
MAXT
=
16 kA = 8 x I
n
I
REF
=
5 % = 50 mA
Setting value scaled to secondary
level
R
CT
=
6
R
W
=
0.4 
I
MAXF
=
25 kA
Maximum secondary voltage during a through fault (Equation
7.3.1-1):
V 2.514.06
2000
1
16000
S
V
Conclusion: The knee point voltage of 100 V is acceptable being
about twice the V
S
.
Serial resistance for the relay input (Equation 7.3.1-2):
R
S
512
005
1024 1000
.
.
Maximum peak voltage during inside fault using a linear model
for CT (Equation 7.3.2-1):
kV 6.12)10004.06(
2000
1
25000
p
V
Approximation of peak voltage during inside fault using a non-
linear model for a saturating CT (Equation 7.3.2-2):
kV 2.3)10012600(10022
sp
V
This is a too high value and a VDR must be used to reduce the
voltage below 3 kV.
A zinc oxide varistor (i.e. VDR, METROSIL) of 1 kV will limit
the voltage. Using a 400 J model allows two 20 VA CTs feeding
ten times their nominal power during one second before the
energy capacity of the varistor is exceeded.

Table of Contents

Related product manuals