7.3 Calculating the stabilizing
resistance RS, VDR value and actual
sensitivity
VAMP 24h support phone +358 (0)20 753 3264
7.3.4. Example
Setting value scaled to secondary
level
Maximum secondary voltage during a through fault (Equation
7.3.1-1):
V 2.514.06
2000
1
16000
S
V
Conclusion: The knee point voltage of 100 V is acceptable being
about twice the V
S
.
Serial resistance for the relay input (Equation 7.3.1-2):
R
S
512
005
1024 1000
.
.
Maximum peak voltage during inside fault using a linear model
for CT (Equation 7.3.2-1):
kV 6.12)10004.06(
2000
1
25000
p
V
Approximation of peak voltage during inside fault using a non-
linear model for a saturating CT (Equation 7.3.2-2):
kV 2.3)10012600(10022
sp
V
This is a too high value and a VDR must be used to reduce the
voltage below 3 kV.
A zinc oxide varistor (i.e. VDR, METROSIL) of 1 kV will limit
the voltage. Using a 400 J model allows two 20 VA CTs feeding
ten times their nominal power during one second before the
energy capacity of the varistor is exceeded.