EasyManua.ls Logo

VAMP 265 - 7.2.1. CT Requirements

VAMP 265
220 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical description
7 Applications
7.2 Restricted earth fault protection
for a transformer with neutral
connection
VM265.EN011
155
7.2.1. CT Requirements
Any difference between the CTs will give a misleading residual
current signal to the relay. Especially during heavy through
faults (i.e. the fault is outside the protected zone) the dissimilar
saturation of the CTs should not yield to a REF trip. On the
other hand a very high fault current causing an unselective
earth fault start or trip is not a fatal error.
Class X CT
In restricted earth fault protection the high and low side CTs
should give similar responses even for high over currents.
Class X CTs will fulfil this requirement. Their performance is
defined in terms of a knee-point voltage (V
KP
), the magnetizing
current at the knee point voltage and the resistance of the
secondary winding at +75 °C.
Knee point voltage (V
KP
) is the secondary voltage at which a 50
% increase of primary current is needed to increase the
secondary voltage by 10 %.

Table of Contents

Related product manuals