9.2.2. Test voltages
Insulation test voltage (IEC 60255-5)
Class III
2 kV, 50 Hz, 1 min
Surge voltage (IEC 60255-5)
Class III
5 kV, 1.2/50 s, 0.5 J
9.2.3. Mechanical tests
Vibration (IEC 60255-21-1)
10 ... 60 Hz, amplitude ±0.035 mm
Class I
60 ... 150 Hz, acceleration 0.5g
sweep rate 1 octave/min
20 periods in X-, Y- and Z axis direction
Shock (IEC 60255-21-1)
half sine, acceleration 5 g, duration 11 ms
Class I
3 shocks in X-, Y- and Z axis direction
9.2.4. Environmental conditions
Operating temperature
-10 to +55 C
Transport and storage temperature
-40 to +70 C
Relative humidity
< 75% (1 year, average value)
< 90% (30 days per year, no condensation
permitted)
9.2.5. Casing
Degree of protection (IEC 60529)
IP20
Dimensions (W x H x D)
208 x 155 x 225 mm
Material
1 mm steel plate
Weight
4.2 kg
Colour code
RAL 7032 (Casing) / RAL 7035 (Back plate)
9.2.6. Package
Dimensions (W x H x D)
215 x 160 x 275 mm
Weight (Terminal, Package and Manual)
5.2 kg