2.7 Earth fault protection I0>
(50N/51N)
VAMP 24h support phone +358 (0)20 753 3264
Io
Io2
IoCalc
IoPeak
Io2Peak
I‟oCalc
The supervised value
according the parameter
"Input" below.
Pick-up value scaled to
primary value
Pick-up setting relative to the
parameter "Input" and the
corresponding CT value
DT
IEC
IEEE
IEEE2
RI
PrgN
Delay curve family:
Definite time
Inverse time. See chapter 2.13.
DT
NI
VI
EI
LTI
Parame-
ters
Delay type.
Definite time
Inverse time. See chapter 2.13.
Definite operation time (for
definite time only)
Inverse delay multiplier (for
inverse time only)
Io1
Io2
IoCalc
Io1Peak
Io2Peak
I‟oCalc
X1-7&8. See chapter 8
X1-9&10
IL1 + IL2 + IL3
X1-7&8 peak mode
X1-9&10 peak mode
I‟L1 + I‟L2 + I‟L3
User's constants for standard
equations. Type=Parameters.
See chapter 2.13.
For details of setting ranges see chapter 9.3.
Set = An editable parameter (password needed)
C = Can be cleared to zero
F = Editable when force flag is on