Subject to modification! Updated 10/2017
Table 12 contains the default values that are saved for Germany,
Austria, France, Italy and the Netherlands.
Grid parameters
Country
FGRID_MIN
(in Hz)
FGRID_MAX
(in Hz)
UGRID_MIN
(in V)
UGRID_MaX
(in V)
UGRID_MAX10
(in V)
Germany
47.50
51.50
184
264
253
Austria
47.50
51.50
184
264
255
France
47.50
51.50
184
264
253
Italy
47.50
51.50
184
264
253
Netherlands
47.50
51.50
184
264
253
Table 12: Grid parameter default settings
Note: If the Automatic option is not selected, the following
parameters can also be set to suit the individual requirements of
the grid operator:
Minimum grid frequency (FGRID_MIN)
Maximum grid frequency (FGRID_MAX)
Minimum grid voltage (UGRID_MIN)
Maximum grid voltage (UGRID_MAX)
Maximum grid voltage for 10 minutes (UGRID_MAX10)