11.3 Checking the system parameters
The system parameters are checked via the web interface. To do so,
please observe Chapter 9.
11.3.1 Checking the current sensor values
Select the System page.
Check the current sensor values (I grid L1, I grid L2 and I grid
L3) on reasonable values:
If a current sensor value is approx. 0, although the phase is
currently loaded, the connection between current sensor and
energy storage system might be faulty.
If necessary, load all phases separately: Switch on consumers
deliberately.
If necessary, check the current through all three phases with
the clamp-on ammeter!