EasyManua.ls Logo

Varta element Series - Table 7: Technical Parameters - Expansion Stage Element 9; Table 8: Technical Parameters - Expansion Stage Element 12

Varta element Series
159 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Subject to modification! Updated 10/2017
EXPANSION STAGE ELEMENT 9
Nominal capacity
AC charge power
AC discharge power
Battery inverter structure
Dimensions in mm (W x H x D)
Weight (incl. battery modules)
Installation location
Grid connection
Make current
Maximum output residual current
Internal consumption
optimisation
Power measurement
System transport
Packaging in mm (W x H x D)
Grid system fusing
9.8 kWh
3.4 kW
3.0 kW
without isolation transformer
600 x 1,176 x 500
145 kg
inside the building
400 V AC, 3-phase, 50 Hz
< max. operating current
for input and output
max. 6 A for 100 μs
3-phase, regulated
3-phase, via current sensor
vertical on a pallet
700 x 1,325 x 600
16 A (B-character)
Table 7: Technical parameters expansion stage element 9
EXPANSION STAGE ELEMENT 12
Nominal capacity
AC charge power
AC discharge power
Battery inverter structure
Dimensions in mm (W x H x D)
Weight (incl. battery modules)
Installation location
Grid connection
Make current
Maximum output residual current
Internal consumption
optimisation
Power measurement
System transport
Packaging in mm (W x H x D)
Grid system fusing
13 kWh
4 kW
3.7 kW
without isolation transformer
600 x 1,176 x 500
165 kg
inside the building
400 V AC, 3-phase, 50 Hz
< max. operating current
for input and output
max. 6 A for 100 μs
3-phase, regulated
3-phase, via current sensor
vertical on a pallet
700 x 1,325 x 600
16 A (B-character)
Table 8: Technical parameters expansion stage element 12

Table of Contents

Other manuals for Varta element Series