EasyManua.ls Logo

Varta element Series - Table 14: Setting as Per Q(P) Characteristic

Varta element Series
159 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
121
General
Operation
Installation
Operation (Service)
Maintenance
Table 14: Setting as per Q(P) characteristic
Time delay: Enter the time in s, after which the reactive
power is to be adjusted.
Minimum power: Enter the minimum power in %, up to
which the reactive current is not controlled.
Setting as per Q(U) characteristic
Reactive power function: Select Q(U) characteristic from
the drop-down list.
QUX1 to QUX4: Enter the settings for QUX1 to QUX4 by
using the numerical input fields. You can find the settings in
Figure 28.
QUY1 to QUY4: Enter the settings for QUY1 to QUY4 by
using the numerical input fields. You can find the settings
in Table 15.

Table of Contents

Other manuals for Varta element Series