Model Number GXT5-EBC36VRT2U GXT5-EBC48VRT2U
Used W/UPS Model 750 – 1,000 VA Models 1,500 – 2,000 VA Models 3,000 VA Models
Dimensions, D×W×H, in. (mm)
Unit
14.6 x 16.9 x 3.3
(370 × 430 × 85)
19.7 x 16.9 x 3.3
(497 × 430 × 85)
23.7 x 16.9 x 3.3
(602 × 430 × 85)
Shipping 24.3 x 22.4 x 10.3 (617 x 570 x 262)
Weight, lb.(Kg)
Unit 48.4 (22) 57.3 (28.5) 97.84 (44.38)
Shipping 91.3 (41.5) 86 (41.5) 104.9 (47.6)
Battery
Type Valve-regulated, non-spillable, lead acid
Qty × V
Two parallel strings of three 12 V/9 Ah
batteries in series.
Two parallel strings of four 12 V/9 Ah
batteries in series.
Two parallel strings of six 12 V/9 Ah
batteries in series.
Backup time See appropriate table for model size in Battery Run Times on page99.
EBC Breaker Size 50 A 63 A
Environmental Requirements
Operating Temperature,
°F (°C)
32 to 104 (0 to 40)
Extended Operating
Temperature, °F (°C)
32 to 122 (0 to 50); output derated by 1% per 1 °C above 40 °C
Storage Temperature,
°F (°C)
5 to 104 (-15 to 40) High ambient temperatures will reduce battery life
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 77 °F (25 °C) without derating
Agency
Safety EN 62040-1:2008+A1:2013; GS mark; UL 1778 5th Edition and CSA 22.2 No. 107.3
EMC EN 62040-2:2006 EN 61000-3-2:2014 EN 61000-3-3:2013
Safety UL 1778 5th Edition and CSA 22.2 No. 107.3
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62.41 Category B
RFI/EMI FCC Part 15 (Class A)
Table 8.8 External Battery Cabinet Specifications, 750 VA to 3000 VA Models
8 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp. 97
Vertiv™ Liebert® GXT5 UPS Installer/User Guide