Load
Internal
Battery
Only
Number of External Battery Cabinets
1 2 3 4 5 6 7 8 9 10
50 375 375 25.7 103.2 178.9 255.9 337.1 420.2 505.5 592.1 672.6 761.7 852.0
60 450 450 20.4 84.8 149.0 212.4 280.7 350.0 420.3 492.6 565.3 631.7 706.8
70 525 525 16.7 72.0 128.2 183.8 238.8 298.1 358.3 419.6 481.8 544.9 607.0
80 600 600 14.1 59.7 112.1 161.6 208.6 260.6 313.2 366.4 420.4 475.8 531.1
90 675 675 12.1 53.0 99.5 143.9 188.3 232.1 278.8 326.1 374.6 423.3 473.1
100 750 750 10.5 46.3 88.3 130.2 170.8 208.8 251.5 294.1 337.6 381.7 426.5
Table 8.11 Battery Run Time, 750 VA Models (continued)
Load
Internal
Battery
Only
Number of External Battery Cabinets
1 2 3 4 5 6 7 8 9 10
% VA W Minutes
10 100 100 101.8 332.7 584.9 841.2 1114.7 1373.2 1590.9 1750.8 1873.0 1969.6 2047.7
20 200 200 50.1 179.8 311.9 453.2 595.8 736.7 888.2 1042.4 1199.1 1340.5 1476.5
30 300 300 33.7 127.1 218.3 316.1 416.5 519.9 620.3 724.8 833.9 944.6 1056.5
40 400 400 23.8 95.8 168.9 239.3 316.4 394.3 474.5 555.3 629.9 713.6 798.3
50 500 500 17.8 76.3 135.1 193.0 251.8 314.0 377.3 443.1 506.8 573.0 632.6
60 600 600 14.1 59.7 112.1 161.6 208.6 260.6 313.2 366.4 420.4 475.8 531.1
70 700 700 11.5 50.7 95.3 139.4 181.7 224.1 268.6 315.0 361.0 428.6 457.6
80 800 800 9.6 43.3 83.4 120.8 160.1 197.6 235.3 275.3 316.3 357.1 399.0
90 900 900 8.1 38.2 73.0 107.4 141.0 174.8 206.9 241.5 277.6 314.0 250.4
100 1000 1000 6.8 33.3 62.8 94.6 125.7 156.3 187.0 216.1 248.0 280.4 313.1
Table 8.12 Battery Run Time, 1000 VA Models
100 Proprietary and Confidential ©2024 Vertiv Group Corp. 8 Specifications
Vertiv™ Liebert® GXT5 UPS Installer/User Guide